The GADP ground fault
alarm unit with its built in pulsing capability,
paired with the OHMNI-PM resistor, is ideal for
resistance grounded power systems where indication
of the severity of the fault, indication of the
faulted phase and the capability to locate the
fault is required.
The GADP relay works on the principle of a change
in line-to-ground voltage that occurs when a fault
appears on one of the lines of a high resistance
grounded system. For the purpose of measurement
a resistor divider, I-GARD Type DDR2 is used which
provides a proportional low voltage signal to
the relay to indicate which phase is faulted and
the fault level as a percentage of the maximum
fault level of 100% (representing a complete short
to ground on one phase).
Alarm
on first fault at 50% of fault current

Phase and fault magnitude
indication

built in pulsing capability

Available for 120V, 240V,
240V, 480V and 600V systems
|