To service the special
needs of the mining industry I-Gard has developed
the GCHK-100 ground fault relay to improve safety
for personnel and equipment in underground or
above ground applications. Detection of ground
faults is important where safety from electric
shock and fire risk can occur and cause serious
equipment and personnel hazards.
The relay is designed for use with Resistance-Grounded
systems up to 4160V but could be used with Grounded
Systems in branch circuit applications where Load
current is limited to 800 Amps.
Ground
Fault Detection, with 13 adjustable pickup settings
from 0.25 - 12.5A, and eight adjustable time delay
settings from 0.020 - 10s

ground circuit checking
through the use of an auxiliary pilot ground conductor

Frame touch voltage protection,
with four adjustable pickup levels from 40 - 100V

|